Rockliner U-values

The table below shows the thermal improvements to an un-insulated (brick and dense block) cavity wall when filled with Rockwool HP Energy Saver.

Table showing enhancement of U-values using Rockliner

HP EnergySaver thickness related to cavity widthU-value of wall filled with blown EnergySaverEnhanced U-value when dry lined with 52.5mm Rockliner
50mm0.580.35
65mm0.480.31
75mm0.430.29
100mm0.340.24

 

The contractor will be required to state the U-value achieved on their submission to SEI on completion of works.